Split Core Hall Effect AC/DC Current Sensor CYHCS-EKOS, Output: 2.5 V DC ±1.5 V AC/DC, Power Supply: +5 V DC ± 5%, Window: Ø 80 mm
| Quantity | Unit price |
|---|---|
| Until 4 |
€170.35
|
| From 5 |
€154.85
|
| From 10 |
€140.78
|
Article not in stock, delivery time 3-4 Weeks
Product information "Split Core Hall Effect AC/DC Current Sensor CYHCS-EKOS, Output: 2.5 V DC ±1.5 V AC/DC, Power Supply: +5 V DC ± 5%, Window: Ø 80 mm"
This Hall Effect current sensor is based on the open-loop principle and designed with a split core and high galvanic isolation between the primary conductor and secondary circuit. It can be used for the measurement of AC/DC current etc. The output of the transducer reflects the real wave of the current-carrying conductor.
Applications
- Photovoltaic equipment
- Frequency conversion timing equipment
- Various power supply
- Uninterruptible power supplies (UPS)
- Electric welding machines
- Electrolyzing and electroplating equipment
- Electrically powered locomotive
- Electric power network monitoring
Features
- Excellent accuracy
- Very good linearity
- Less power consumption
- Split core window structure
- Electrically isolating the output of the transducer from the current-carrying conductor
- No insertion loss
- Current overload capability
Information about product safety:
Manufacturer/ EU Responsible Person:
Company name: ChenYang Technologies GmbH & Co.KG
Address: Markt Schwabener Str. 8; 85464 Finsing; Deutschland
E-Mail: info@chenyang.de
Phone: +49 8121 2574100
| Accuracy: | 1% |
|---|---|
| Current Type: | AC/DC |
| Direction: | bidirectional |
| Frequency Bandwith: | DC~6kHZ |
| Linearity: | 1,0% |
| Nominal Input Current: | 0-500A, 0-1000A, 0-2000A, 0-5000A, 0-8000A, 0-10000A, 0-12000A, 0-15000A, 0-20000A |
| Operating Temperature: | -25°C ~ +85°C |
| Output Signal: | +2,5 V ± 1,5 V AC/DC |
| Power Supply: | +5 V DC |
| Sensor Type: | Open-Loop |
| Window Size (mm): | ø 80 |
| Window Type: | Round |
Manufacturer:
Company name: ChenYang Technologies GmbH & Co.KG
Address: Markt Schwabener Str. 8; 85464 Finsing; Deutschland
E-Mail: info@chenyang.de
Phone: +49 8121 2574100